FANUC 0i-F DS0306 APC ALARM: BATTERY VOLTAGE 0 after weekend shutdown, what to check?

Question

I'm getting a DS0306 APC ALARM: BATTERY VOLTAGE 0 on my FANUC 0i-F controller. The machine was off over the weekend, and now this alarm popped up at power-up. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

The DS0306 alarm on a FANUC 0i-F controller indicates that the absolute position detector battery voltage has dropped to a level where position data can no longer be held, or a Pulsecoder was powered for the first time. This often happens after the machine has been off for an extended period with a depleted battery. The primary suspect is the battery itself or its connection.

Likely causes and checks

1Battery exhausted while the machine was off

Points to it
The battery voltage dropped below the critical level needed to retain position data because the machine was powered off for an extended period, such as over a weekend. Earlier DS0307 or DS0308 warnings might have been ignored.
Check
Read DGN 3019 to identify the affected detector. Replace the battery with the machine turned on and E-stop applied. Afterward, you will need to set the reference position (DS0300).

2Battery replaced with power off

Points to it
If the battery was replaced while the machine's power was off, the absolute position data would have been lost during the change, triggering the alarm.
Check
The battery should be replaced again with the machine powered on. The position must then be re-established.

3Battery cable or connector fault

Points to it
Even if the battery itself is new and measures good, a faulty cable or connector can prevent the voltage from reaching the absolute position detector.
Check
Inspect the battery cable and its connector leading to the amplifier for the specific axis experiencing the alarm.

4New Pulsecoder powered for the first time

Points to it
This alarm is expected when a new motor or Pulsecoder is installed and powered up for the very first time, as there is no initial position data.
Check
This is a normal occurrence in this scenario. Proceed to set the reference position according to the machine builder's procedure.

Next check: Given the machine was off over the weekend, the most likely cause is an exhausted battery. You should first check DGN 3019 for the affected detector and prepare to replace the battery with the machine powered on and E-stop engaged.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.