Fireye NX6100 F16: primary air pressure not proven, what to check?

Question

My NX6100 controller is throwing an F16 fault during burner startup, specifically at status 07. This is for the primary air, not the main combustion air. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

The Fireye NX6100 controller's F16 fault indicates that the optional primary air pressure switch did not register air pressure when required, typically from status 07 onwards. This fault is distinct from F14, which relates to the main combustion air switch, and F17, which signals primary air pressure when it shouldn't be present. The NX6100 is a microprocessor-based flame safeguard and parallel positioning combustion controller.

Likely causes and checks

1Primary air fan or path issue

Points to it
The primary air fan might not be running or its air path could be restricted, preventing air from reaching the switch.
Check
Confirm that the primary air source is operating and its air path is clear of obstructions.

2Primary air switch setpoint or sensing line problem

Points to it
Air may be present, but the primary air switch is not making contact, possibly due to an incorrect setpoint or an issue with its sensing line.
Check
Measure the differential pressure at the primary air switch and compare it against its specified setpoint.

Next check: After checking the primary air fan/path and the switch setpoint/sensing line, ensure that option 6.x is set correctly, as incorrect settings can also lead to air pressure faults.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.