Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000) fault T07:C41: Nonvolatile fault: load failed, controller type mismatch

Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000)faultFault code list 1756-RD001F (September 2025)

Loading from nonvolatile memory failed because of a controller type mismatch: the project on the card was saved for a different controller type. Rockwell’s corrective action: change to a controller of the correct type, or download the project and store it on the memory card.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000). InduQT compares the evidence and suggests the next useful checks.

Try Free PLC Fault Diagnostic

When it happens

Likely causes and checks

1Controller replaced with a different catalog number

Points to it
Fault after a hardware swap; the card came from the old controller.
Check
Compare the installed controller catalog number with the controller type in the project.

2Memory card from another machine

Points to it
Card was moved or reused from a different system.
Check
Confirm which project is on the card before loading or overwriting it.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.