Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000) fault T07:C42: Nonvolatile fault: load failed, revision mismatch

Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000)faultFault code list 1756-RD001F (September 2025)

Loading from nonvolatile memory failed because the firmware revision of the project in nonvolatile memory does not match the firmware revision of the controller. Rockwell’s corrective action: update the controller firmware to the same revision as the project in nonvolatile memory.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000). InduQT compares the evidence and suggests the next useful checks.

Try Free PLC Fault Diagnostic

When it happens

Likely causes and checks

1Replacement controller shipped with different firmware

Points to it
Fault after a controller swap; same catalog number, different firmware revision.
Check
Read the controller firmware revision and compare it with the project revision.

2Controller firmware changed after the card image was stored

Points to it
Firmware was updated but the card still holds the older project.
Check
Check the firmware history and when the card image was last stored.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.