Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT fault NC 0x4550: Position lag monitoring (following error) (17744)

Beckhoff TwinCAT 3 (XAR/XAE) with EtherCATfaultTwinCAT 3.1; ADS Basics 2.6.2, EtherCAT System Manual 6.1.0, NC Errors 2.5.1

Beckhoff: while position lag monitoring was active, the lag error (set position minus actual position) exceeded the Maximum Position Lag Value for longer than the Maximum Position Lag Filter Time. The NC axis is stopped immediately by direct shutdown and set to the logical state "Error".

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT. InduQT compares the evidence and suggests the next useful checks.

Try Free PLC Fault Diagnostic

When it happens

Likely causes and checks

1Mechanical: obstruction, brake not released, binding or a crash

Points to it
Lag grows while actual velocity drops; torque at its limit in the drive.
Check
Trace set/actual position, lag and torque in Scope View; inspect the axis mechanics and brake.

2Motion profile beyond what the drive/motor can follow

Points to it
Lag peaks at acceleration ramps; drive at current limit.
Check
Compare commanded acceleration/velocity with motor and drive capacity.

3Scaling, encoder or tuning error

Points to it
Lag grows steadily even with slow moves, or the axis runs the wrong way.
Check
Check encoder scaling, direction and the position controller settings against commissioning values.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
Position Lag MonitoringPosition lag monitoring enableTRUE enables monitoring.
Maximum Position Lag ValueMaximum position lagUpper limit that must not be exceeded for longer than the filter time.
Maximum Position Lag Filter TimeLag filter timeHow long the limit may be exceeded before 0x4550.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.