Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT fault NC 0x4260: Controller enable missing (16992)

Beckhoff TwinCAT 3 (XAR/XAE) with EtherCATfaultTwinCAT 3.1; ADS Basics 2.6.2, EtherCAT System Manual 6.1.0, NC Errors 2.5.1

Beckhoff: the controller enable for an axis or a coupled slave axis is not present (axis interface PlcToNc). The error occurs if controller enable is withdrawn while an axis or group (also a master/slave group) is being actively positioned, and if a PTP axis or coupled slave axis is started without controller enable.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT. InduQT compares the evidence and suggests the next useful checks.

Try Free PLC Fault Diagnostic

When it happens

Likely causes and checks

1PLC logic removes enable during a move (e.g. MC_Power Enable tied to a condition that drops)

Points to it
Error at the moment the enable condition changes; Scope shows Enable falling while the axis is busy.
Check
Trace MC_Power Enable/Status and the move FB Busy in Scope View.

2Move started before MC_Power reported Status = TRUE

Points to it
Error at start of motion, not during it.
Check
Check the sequence waits for MC_Power.Status before starting moves or couplings.

3Coupled slave axis not enabled

Points to it
Master moves, error raised for the group or slave.
Check
Check enable on every axis of the coupled group.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.