Siemens SIMATIC S7-1500 warning OB122: I/O access error
The operating system calls OB122 when an error occurs during direct access to I/O data while an instruction executes, for example a read error on direct access to an input module, provided the block does not use GET_ERROR or GET_ERR_ID. Fault_ID 16#42 is a read error, 16#43 a write error. On the S7-1500 the CPU always stays in RUN on an I/O access error and writes a diagnostics buffer entry, even without OB122; on S7-300/400 a missing OB122 puts the CPU in STOP.
Diagnose this with AI
Try Free PLC Fault Diagnostic Upload a keypad photo, the fault history or a parameter export from your Siemens SIMATIC S7-1500. InduQT compares the evidence and suggests the next useful checks.
When it happens
- RUN, when the program directly reads or writes I/O (e.g. %IW…:P) of a module that is not available
Likely causes and checks
1Module or station not available at the time of direct access
- Points to it
- OB122 together with OB83 or OB86 events for the same hardware.
- Check
- Check the module or station status in Online & diagnostics.
2Direct access to an address with no configured module
- Points to it
- Error repeats every cycle at the same address.
- Check
- Compare the address in the program with the hardware configuration.
Telling it apart
- An I/O access error on the S7-1500 never stops the CPU on its own; if the CPU stopped, look for OB121 or OB80 entries instead.
- A read error (16#42) means the program did not get a valid value for that input; check what the logic does when the access fails.
Evidence to collect
- Diagnostics buffer export
- OB122 start information (BlockNr, Fault_ID, Area, Width), if logged
- Address accessed and the hardware configuration
- Module or station status at the time