ATV320 trips SCF3 at start, after washdown, what to check?

Question

My Altivar ATV320 drive is tripping on SCF3 (Ground Short Circuit) right at startup. This started happening after a recent washdown of the machine. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

An SCF3 fault on a Schneider Altivar ATV320 drive indicates a significant earth leakage current at the drive's output. This fault often occurs at start-up or while running, especially with multiple motors connected to one drive or in damp conditions. Since it happened after a washdown, insulation issues are highly probable.

Likely causes and checks

1Motor cable insulation to ground

Points to it
Water ingress from the washdown could have damaged or compromised the insulation of the motor cables, leading to leakage to ground. This is a common cause, especially if cables run through wet conduits.
Check
Lock out the machine and confirm the DC bus voltage is below 42 Vdc. Disconnect the motor cable from the drive and use a megohmmeter to test each conductor to ground.

2Motor winding insulation to ground

Points to it
Similar to cable insulation, the motor windings themselves could have been affected by moisture from the washdown, leading to a breakdown in insulation to ground.
Check
If the cable insulation tests good, disconnect the motor from the drive and megger the motor windings to ground.

3Leakage from several motors or long cables in parallel

Points to it
If multiple motors are connected to this single drive or if the total cable length is extensive, the cumulative capacitive leakage can trigger an SCF3 fault, especially if dampness exacerbates the issue.
Check
If insulation tests for both cable and motor are good, consider connecting chokes in series with the motor and reducing the switching frequency (SFR) parameter on the drive.

4Speed loop or brake settings

Points to it
While less likely given the washdown context, incorrect speed loop or brake adjustments can sometimes contribute to SCF3 trips, particularly on brake-controlled axes around brake release.
Check
Check the speed loop and brake adjustment parameters. You might also consider increasing the [Time to restart] TTR parameter.

Next check: After addressing the cause, an SCF3 fault requires a power reset of the device unless the [Extended Fault Reset] HRFC parameter is set to 'Yes', in which case it can be cleared manually with the [Fault Reset Assign] rsf parameter.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.