PowerFlex 525 F007: motor overload trips after a few minutes, what to check?

Question

My PowerFlex 525 drive is faulting F007 (Motor Overload) after running for several minutes at constant speed. The motor feels hot to the touch. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

The F007 Motor Overload fault on a PowerFlex 525 drive indicates that the drive's internal electronic motor overload protection (I²t, Class 10) has tripped. This occurs when the output current remains above the configured P033 [Motor OL Current] for an extended period. Common scenarios include sustained heavy loads, repeated starts, or long acceleration times.

Likely causes and checks

1Motor genuinely overloaded

Points to it
The motor is drawing more current than its nameplate rating due to excessive mechanical load on the driven machine.
Check
Measure the drive's output current (parameter b003) and compare it to the motor's nameplate Full Load Amps (FLA). Inspect the driven machine for any binding, wear, or process conditions that could be causing an overload.

2P033 [Motor OL Current] set too low

Points to it
The drive's internal overload protection parameter P033 is configured below the motor's actual nameplate FLA, causing it to trip prematurely even under normal operating conditions.
Check
Verify that parameter P033 [Motor OL Current] matches the motor's nameplate FLA, considering any site-specific service factor practices.

3Boost too high at low speed

Points to it
If the drive is running at low speeds with a high V/Hz boost setting (A530 [Boost Select]), it can cause excessive current draw and lead to an overload trip, even with a light load.
Check
Review the A530 [Boost Select] setting to ensure it is appropriate for the load type and check the overall V/Hz settings.

4Low-speed derating not accounted for

Points to it
Self-cooled motors may require derating of their overload protection at low speeds, which the drive's I²t function (A493 [Motor OL Select]) might not be configured to handle.
Check
Examine parameter A493 [Motor OL Select] to ensure the I²t function's derating is correctly set for the motor's cooling characteristics, especially if the fault only occurs at low speeds.

Next check: Given the motor is hot and the fault occurs after several minutes, the most likely cause is a genuine motor overload. Start by measuring the drive's output current (b003) and comparing it to the motor's nameplate FLA, then inspect the driven machine for mechanical issues.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.

Related questions

Different symptoms on your machine?

Describe the fault or upload a photo, and InduQT checks it against the manufacturer manuals. Share the result here when it helps someone else.

Ask the free troubleshooter