PowerFlex 525 F033 Auto Rstrt Tries: what to check first?

Question

My PowerFlex 525 drive on a pump application keeps faulting with F033 Auto Rstrt Tries. This happens after it tries to clear some other fault multiple times. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

Fault F033 on a PowerFlex 525 drive indicates that the drive attempted to reset a fault and resume operation for the configured number of attempts (A541 [Auto Rstrt Tries]) but failed. This is a Type 2 fault, meaning it cannot be auto-reset. The F033 fault itself is not the root cause; it points to an underlying Type 1 fault that repeatedly tripped the drive.

Likely causes and checks

1A recurring underlying fault

Points to it
The drive repeatedly encountered the same Type 1 fault, which it tried to clear and restart from, eventually exhausting the allowed retry attempts.
Check
Examine the fault queue (b008, b009, and F604–F610) to identify the specific Type 1 fault that kept recurring. Then, troubleshoot that particular fault.

2Supply problems that outlast the restart delay

Points to it
Transient supply issues (like F004 or F005) caused the drive to trip, and the disturbance lasted longer than the configured auto restart delay, preventing successful restarts.
Check
If the underlying faults are F004 (UnderVoltage) or F005 (OverVoltage), compare the duration of the supply disturbance with A542 [Auto Rstrt Delay] and address the power supply issue.

3Restart delay too short for the condition to clear

Points to it
Conditions like overheating (F008 Heatsink OvrTmp or F007 Motor Overload) persisted because the auto restart delay was insufficient for the drive or motor to cool down before another restart attempt.
Check
If the underlying fault is F008 or F007, investigate the cause of the overheating. A longer delay would only mask the underlying problem.

Next check: The most crucial step is to identify the original Type 1 fault that the drive was repeatedly trying to clear. Check the fault queue (b008, b009, and F604–F610) to find this information, then troubleshoot that specific fault.