Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT fault AL 0x001E: Invalid input configuration
Beckhoff: the SyncManager configuration for input process data is invalid. Raised on P→S (and in SAFEOP/OP), resulting state SAFEOP + error.
Diagnose this with AI
Try Free PLC Fault Diagnostic Upload a keypad photo, the fault history or a parameter export from your Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT. InduQT compares the evidence and suggests the next useful checks.
When it happens
- At EtherCAT startup on the transition PREOP to SAFEOP
- After a device was replaced or its process data were edited
Likely causes and checks
1Configured device revision or ESI differs from the installed device
- Points to it
- Fault after a device swap or firmware update.
- Check
- Compare configured and found vendor, product code and revision with an online scan.
2Input process data edited to a combination the device does not support
- Points to it
- Fault after changes on the Process Data tab.
- Check
- Restore the default PDO selection and re-apply only options from the device documentation.
Telling it apart
- 0x001E is the input side (SM3), 0x001D the output side; 0x0024 is an input PDO mapping mismatch rather than the SyncManager setting.
Evidence to collect
- Logger export with the AL status code
- Process Data tab screenshot
- Online scan result (vendor, product code, revision)
- ESI file version used in the project
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.