Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT fault AL 0x001E: Invalid input configuration

Beckhoff TwinCAT 3 (XAR/XAE) with EtherCATfaultTwinCAT 3.1; ADS Basics 2.6.2, EtherCAT System Manual 6.1.0, NC Errors 2.5.1

Beckhoff: the SyncManager configuration for input process data is invalid. Raised on P→S (and in SAFEOP/OP), resulting state SAFEOP + error.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT. InduQT compares the evidence and suggests the next useful checks.

Try Free PLC Fault Diagnostic

When it happens

Likely causes and checks

1Configured device revision or ESI differs from the installed device

Points to it
Fault after a device swap or firmware update.
Check
Compare configured and found vendor, product code and revision with an online scan.

2Input process data edited to a combination the device does not support

Points to it
Fault after changes on the Process Data tab.
Check
Restore the default PDO selection and re-apply only options from the device documentation.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.