Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT fault AL 0x0030: Invalid DC SYNC configuration

Beckhoff TwinCAT 3 (XAR/XAE) with EtherCATfaultTwinCAT 3.1; ADS Basics 2.6.2, EtherCAT System Manual 6.1.0, NC Errors 2.5.1

Beckhoff: the distributed clock configuration is invalid due to application requirements. Raised on P→S, S→O or in OP; resulting state PREOP + error or SAFEOP + error.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT. InduQT compares the evidence and suggests the next useful checks.

Try Free PLC Fault Diagnostic

When it happens

Likely causes and checks

1DC operating mode not supported with the selected process data or cycle time

Points to it
Fault after changing the DC mode (e.g. FreeRun/SM-synchron/DC) or the task cycle.
Check
Compare the DC tab setting and the task cycle time with what the device documentation allows.

2Cycle time outside the device’s supported range

Points to it
Related codes 0x0035 (DC invalid sync cycle time) or 0x0036 (Sync0 cycle time) appear on other devices.
Check
Check the minimum/maximum cycle time of the device.

3Reference clock set manually to a device without DC support

Points to it
Beckhoff: slaves will not switch to OP and report PREOP_ERR; logger "is reference clock device, but does not support dc!".
Check
Check the reference clock selection in the master’s DC settings.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
Slave DC tabOperation mode (FreeRun / SM-synchron / DC)Must be a mode the device supports with the selected PDOs.
Task cycle timeSync task cycleMust lie within the device’s supported range.

Evidence to collect