Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT fault AL 0x0030: Invalid DC SYNC configuration
Beckhoff: the distributed clock configuration is invalid due to application requirements. Raised on P→S, S→O or in OP; resulting state PREOP + error or SAFEOP + error.
Diagnose this with AI
Try Free PLC Fault Diagnostic Upload a keypad photo, the fault history or a parameter export from your Beckhoff TwinCAT 3 (XAR/XAE) with EtherCAT. InduQT compares the evidence and suggests the next useful checks.
When it happens
- At startup on PREOP to SAFEOP or SAFEOP to OP
- After changing the task cycle time or the DC operating mode of a drive or terminal
Likely causes and checks
1DC operating mode not supported with the selected process data or cycle time
- Points to it
- Fault after changing the DC mode (e.g. FreeRun/SM-synchron/DC) or the task cycle.
- Check
- Compare the DC tab setting and the task cycle time with what the device documentation allows.
2Cycle time outside the device’s supported range
- Points to it
- Related codes 0x0035 (DC invalid sync cycle time) or 0x0036 (Sync0 cycle time) appear on other devices.
- Check
- Check the minimum/maximum cycle time of the device.
3Reference clock set manually to a device without DC support
- Points to it
- Beckhoff: slaves will not switch to OP and report PREOP_ERR; logger "is reference clock device, but does not support dc!".
- Check
- Check the reference clock selection in the master’s DC settings.
Telling it apart
- 0x0030 is a configuration refusal at startup; 0x001A and 0x002C are sync losses in operation.
- 0x0035/0x0036 point specifically to the cycle time.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| Slave DC tab | Operation mode (FreeRun / SM-synchron / DC) | Must be a mode the device supports with the selected PDOs. |
| Task cycle time | Sync task cycle | Must lie within the device’s supported range. |
Evidence to collect
- DC tab of the slave and DC settings of the master
- Task cycle time
- Logger export (reference clock and "DC not synchronized" messages)
- Device documentation of supported DC modes