Danfoss FC 301/302 VFD showing ALARM 84, "No safety option"?

Question

My Danfoss VLT AutomationDrive FC 301/302 VFD is showing ALARM 84. The display says "No safety option". What does this mean and what should I check first to clear it?

Top answer · Written by InduQT from the manufacturer manuals cited below · Nov 4, 2026

ALARM 84 on a Danfoss VLT AutomationDrive FC 301/302 indicates that a safety option, which was previously installed, has been removed without performing a general reset. The VFD expects the safety option to be present. To resolve this, you should first try reconnecting the safety option.

Likely causes and checks

1Safety option removed

Points to it
The VFD detected that a safety option, which was previously configured or present, is no longer connected. This typically happens if the option card was physically removed or became disconnected.
Check
Visually inspect the VFD to ensure that any safety option cards are securely seated in their slots. If an option was intentionally removed, it needs to be reconnected or a general reset performed.

2Loose or faulty connection

Points to it
Even if the safety option is present, a loose connection or a faulty card can trigger this alarm, as the VFD cannot properly communicate with it.
Check
Isolate and lock out power to the VFD. Carefully check the connections of the safety option card. Remove and re-insert the card to ensure it is properly seated. Inspect the card for any visible damage.

Next check: If reconnecting the safety option does not clear the alarm, you may need to perform a general reset of the VFD. According to the manual, "The safety option was removed without applying a general reset. Reconnect the safety option." If the option is confirmed to be present and connected, a reset might be necessary to re-initialize the VFD's configuration.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.