Fireye NX6300 F41: Boiler Pressure or Temperature Limit

Question

I'm getting an F41 fault on my Fireye NX6300 burner control. It seems to happen when the boiler is at high load, or when the steam demand suddenly drops. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 27, 2026

The F41 fault on the Fireye NX6300 indicates either that the boiler's measured pressure or temperature has exceeded a safety limit, or that the sensor itself is not functioning correctly. The specific subset number associated with the fault helps differentiate between these two very different situations. Subset 4 points to a real over-pressure or over-temperature event, while subsets 1-3 and 255 indicate sensor or communication issues.

Likely causes and checks

1Real over-pressure or over-temperature

Points to it
This occurs when the boiler's measured pressure or temperature goes above the controller's safety limit. It often happens if steam demand drops suddenly while the burner remains at high fire, causing the pressure or temperature to rise rapidly.
Check
Trend the steam pressure or water temperature and the firing rate just before the trip. Also, check the modulation setpoint and PID parameters against the safety limit to ensure they are configured correctly.

2Sensor or wiring fault

Points to it
The sensor might be providing incorrect feedback, such as reading below 1V, above 5V, or failing during a test. This indicates a problem with the sensor itself or its electrical connection.
Check
Inspect the sensor wiring and its power supply. Verify that no analog input to the controller exceeds 5V, as this could indicate a sensor issue or incorrect wiring.

3CANbus communications fault

Points to it
A fault in the CANbus communication can prevent the NX6300 from correctly receiving data from the boiler sensor, leading to an F41 fault. This is indicated by subset 255.
Check
Check the CANbus wiring and ensure proper termination to the sensor. Look for other CAN devices that might also be showing errors, which would further point to a communication issue.

Next check: If the fault persists and is not related to a real over-pressure or over-temperature event (i.e., not subset 4), and after checking wiring and sensor feedback, the controller may need to be returned to the supplier.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.