Fireye NX6300 F42: Gas valve leak test failed during startup, what to check?

Question

My burner control, a Fireye NX6300, is throwing an F42 fault during startup. It happens when the leak test runs, and the burner never gets to ignition. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

The Fireye NX6300 F42 fault indicates that the gas valve leak test failed during the startup sequence (status 03-09). This means the controller detected an unexpected pressure behavior in the gas section between the safety shutoff valves. Potential causes include a leaking valve seat, unstable gas supply pressure, or incorrect test parameters.

Likely causes and checks

1Leaking valve seat (upstream or downstream)

Points to it
Gas is either escaping or entering the test section when it shouldn't, causing the pressure to decay or build up unexpectedly during the test.
Check
Observe if the fault consistently occurs at the same step. Have a qualified technician perform a tightness test on the gas safety shutoff valves according to the manufacturer's procedure.

2Low or unstable gas supply pressure

Points to it
The gas pressure in the test section is not within the expected range or fluctuates, interfering with the leak test's ability to accurately monitor pressure changes.
Check
Monitor the gas supply pressure during the leak test and compare it against the nominal pressure configured in the controller. Note if the fault occurs intermittently, especially when other gas-consuming equipment is active.

3Incorrect valve proving test parameters

Points to it
The controller's settings for the leak test, such as nominal pressure, test volume, or allowed leak rate, do not match the actual gas train configuration or operating conditions.
Check
Review the valve-proving option parameters (10.1 to 10.7) in the controller, especially if this is a new installation or if the gas train components have been changed. The test might also take an unusually long time if parameters are wrong.

Next check: First, observe if the F42 fault consistently occurs at the same step during startup or if it's intermittent. This can help differentiate between a persistent leak and a pressure issue. Then, check the gas supply pressure during the test against the nominal pressure set in the controller.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.