SINAMICS G120 CU240E-2 F07801 at start, what to check first?

Question

I'm getting an F07801 fault on my SINAMICS G120 CU240E-2 drive when starting a fan. It trips right at the beginning of the start sequence. What's the most likely cause and what should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

The F07801 fault on a SINAMICS G120 drive indicates that the permissible motor limit current was exceeded. This often occurs at start, during acceleration, or on a load step. Common causes include switching onto a rotating motor, a ramp-up that is too short, or incorrect current limit settings. The specific timing of the fault can help narrow down the cause.

Likely causes and checks

1Switching onto a rotating motor

Points to it
If the motor is still rotating (freewheeling) when the drive attempts to start, it can cause an overcurrent condition if the flying restart function is not enabled or properly configured.
Check
Check if parameter p1200 (flying restart) is enabled. If the trip only occurs when restarting a coasting load, enabling this function is the primary remedy.

2Ramp-up too short or load too high (U/f operation)

Points to it
If the acceleration ramp is too short for the connected load, the motor may draw excessive current during acceleration, leading to an overcurrent trip.
Check
Increase the ramp-up time by adjusting parameter p1120 or reduce the motor load if possible. This is particularly relevant if the fault occurs partway through acceleration.

3Current limit or controller settings are incorrect

Points to it
An incorrectly set current limit or current controller parameters can cause the drive to trip prematurely, even under normal operating conditions.
Check
Verify the current limit setting in p0640. If using vector control, check p1715/p1717. In U/f operation, review parameters p1340–p1346. Also, check if alarm A07409 (U/f current limiting controller active) appears before the trip.

4Motor data or star/delta connection is wrong

Points to it
Incorrect motor data entered during commissioning or an improper star/delta connection can lead to the drive miscalculating motor current and tripping on overcurrent.
Check
Confirm that the motor connection (star/delta) matches the drive's configuration and that the motor rating plate data entered during commissioning is accurate. This is especially relevant if the trip occurred after a motor or converter change.

Next check: Given the fault occurs right at the beginning of the start sequence on a fan (which can freewheel), the first thing to check is whether the drive is attempting to start onto a rotating motor and if the flying restart function (p1200) is enabled.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.