SINAMICS G120 trips F30005 after running a while, what to check?

Question

My SINAMICS G120 drive (CU240E-2) keeps tripping with F30005 after the machine runs for about 20 minutes. I've noticed the A07805 alarm comes on before the trip. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

Fault F30005 on a SINAMICS G120 indicates that the Power Module has been overloaded, meaning its I2t value (r0036) reached 100%. This typically happens when the permissible rated current is exceeded for too long or the load duty cycle is not maintained. The A07805 alarm serves as a warning before the trip occurs.

Likely causes and checks

1Continuous load above the Power Module rating

Points to it
The Power Module is continuously operating above its rated capacity, causing its I2t value to steadily climb until it reaches 100% and trips the drive.
Check
Trend the r0036 (Power unit overload I2t) and the output current. If r0036 climbs steadily and A07805 appears before the trip, consider reducing the continuous load or installing a Power Module with a higher rating.

2Duty cycle not respected

Points to it
The drive is undergoing repeated heavy starts or frequent start/stop cycles that exceed the Power Module's permissible load duty cycle, leading to thermal overload.
Check
Compare the actual start/stop cycle of the machine with the permissible load duty cycle specified for the Power Module. If the trip occurs after several quick starts, this is a likely cause.

3Motor and Power Module current ratings mismatched

Points to it
The motor's rated current is too close to or exceeds the Power Module's rated current, making the Power Module prone to overload under normal operating conditions.
Check
Verify and compare the rated currents of both the motor and the Power Module. Ensure the Power Module is adequately sized for the connected motor.

4Current limit set too high

Points to it
The current limit parameter (p0640) is set significantly above the motor's rated current, allowing the Power Module to draw excessive current for extended periods.
Check
Check parameter p0640. If it is well above the motor's rated current, reduce its value. For U/f operation, also consider reducing p1341 (current limiting controller integral time).

Next check: Given that the A07805 alarm appears before the trip and the fault occurs after running for a while, the most likely cause is a continuous load exceeding the Power Module's rating. Start by trending r0036 and the output current to confirm this.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.