SINAMICS G120 F30001 instantly at power-on, r0949=1: what to check?

Question

My SINAMICS G120 is tripping F30001 instantly at power-on, and r0949 shows a value of 1. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

Fault F30001 on a SINAMICS G120 indicates an overcurrent detected by the Power Module, causing an OFF2 trip. The fault value r0949 helps identify the phase involved, with bit 0 corresponding to phase U. An instant trip at power-on, especially with a specific phase identified, often points to issues with the motor or its cabling.

Likely causes and checks

1Short circuit or ground fault in motor or power cables

Points to it
An instant trip at power-on, even with no load, and r0949 indicating a specific phase (like bit 0 for phase U), strongly suggests a short circuit or ground fault in the motor or its power cables.
Check
Lock out the system, disconnect the motor cable at the converter, and perform an insulation test on the motor and cable, phase-to-phase and to ground.

2Motor data or connection wrong

Points to it
Incorrect motor data or an improper star/delta connection can lead to overcurrents, especially if the fault appeared after commissioning, a motor swap, or a Power Module change.
Check
Verify the motor data against its rating plate and confirm the star/delta connection. If necessary, repeat the commissioning process.

3Motor current much larger than Power Module rating

Points to it
If the motor's rated current significantly exceeds the Power Module's rating, it can cause overcurrent trips, particularly if the motor is larger than the converter.
Check
Compare the motor's rated current with the Power Module's rated current (r0207).

4Line side issues: missing line reactor, interrupted phase, poor supply quality

Points to it
Problems on the line side, such as a missing line reactor, an interrupted phase, or poor supply quality, can cause overcurrents, especially if the fault occurs on power-on or after supply dips.
Check
Check the line reactor connection, inspect all line phases, and assess the quality of the line supply.

Next check: Given the instant trip at power-on and r0949=1 (phase U), the most critical next step is to check for a short circuit or ground fault in the motor or its power cables. Lock out the system, disconnect the motor cable at the converter, and insulation-test the motor and cable phase-to-phase and to ground.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.