Yaskawa GA500 trips oC instantly at start, even unloaded: what to check?

Question

My Yaskawa GA500 drive is faulting with an oC (Overcurrent) fault. It happens instantly when I try to start the motor, even when the motor is disconnected from its load. What should I be looking for first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

An oC fault on a Yaskawa GA500 drive indicates that the output current exceeded the specified overcurrent detection level. An instant trip at start, especially when unloaded, strongly suggests an issue with the motor cable or the motor's insulation. It can also alternate with GF (Ground Fault) or SC (Short Circuit/IGBT Failure) faults.

Likely causes and checks

1Motor cable short or ground, or damaged motor insulation

Points to it
A short circuit or ground fault in the motor cable, or damaged motor insulation, can cause an instantaneous overcurrent when the drive attempts to output voltage.
Check
Disconnect the motor at the drive and use a megohmmeter to test both the cable and the motor insulation. Also, measure the cable-to-ground resistance as directed in the manual.

2Run command while the motor is coasting

Points to it
If the drive receives a run command while the motor is still spinning (coasting), it can cause an overcurrent fault as the drive tries to take control of a moving load.
Check
Check if the motor is still turning when the fault occurs, especially with high-inertia loads like fans. Set parameter b3-01 to 1 (speed search at start) or ensure the motor has come to a complete stop before issuing a run command.

3Acceleration time too short for the inertia

Points to it
If the acceleration time is set too short for the connected load's inertia, the drive may draw excessive current during the ramp-up phase to meet the acceleration demand.
Check
Increase the acceleration time parameters C1-01 (or C1-03/C1-05/C1-07) and consider adjusting the S-curve parameters C2-01 to C2-04. Monitor the output current (U2-05) at the point of fault.

4V/f pattern or torque compensation too high

Points to it
Incorrect V/f pattern settings or excessive torque compensation can lead to higher than necessary current draw, particularly at lower speeds and light loads.
Check
Verify parameters E1-04 to E1-10 against the motor's specifications and reduce the C4-01 [Torque Compensation Gain] if it appears to be set too high.

Next check: Given the instant trip at start, even unloaded, the most critical next step is to disconnect the motor from the drive and perform insulation resistance tests on both the motor cable and the motor itself using a megohmmeter.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.