The short answer
Many machines already have the data you want inside their PLC, a drive or an energy meter, and most of those can be read over Modbus TCP without changing the PLC program. Node-RED (free, runs on the same Raspberry Pi) polls the registers every few seconds, scales them into named values and publishes JSON to MQTT. From there it goes to InduQT like any other sensor. You need the register map from the machine builder or the PLC programmer, and read-only access.
- The machine’s own pressures, temperatures, counts and states, with no new sensors
- No change to the PLC program, read-only
- The same MQTT topics as every other sensor in the plant
- What to buy
- Get the register map
- Import the Node-RED flow
- Set up the MQTT broker (once per plant)
- Check the readings with Claude before you connect anything
- Wire it to InduQT
- What InduQT does with it
What to buy
Polls Modbus and publishes MQTT. Maker: OpenJS Foundation. Maker’s page
Modbus TCP and RTU nodes for Node-RED. Maker: open source. Maker’s page
For meters and drives that only have RS-485. Maker: any.
Runs the MQTT broker and the InduQT bridge (skip it if you already built the gateway). Maker: Raspberry Pi. Maker’s page
Prices are typical street prices in US dollars when we wrote this, not quotes; buy from the maker or a local distributor. InduQT does not sell sensors and is not paid by any maker named here.
Get the register map
Ask the machine builder or whoever programmed the PLC for the Modbus map: register address, data type (16-bit, 32-bit, float), scaling and units for each value. Energy meters and drives publish theirs in the manual. Write it down as a short table before you start; the example uses four holding registers on a press.
| Register | Value | Type | Scaling |
|---|---|---|---|
| 40001 (offset 0) | Hydraulic pressure | int16 | 0.1 bar per count |
| 40002 (offset 1) | Oil temperature | int16 | 0.1 °C per count |
| 40003 (offset 2) | Motor current | int16 | 0.1 A per count |
| 40004 (offset 3) | Cycle count | uint16 | 1 |
Import the Node-RED flow
- Install Node-RED on the Raspberry Pi with the official script, then Menu → Manage palette → Install → node-red-contrib-modbus.
- Menu → Import, paste the flow below, and set the PLC’s IP address and unit id in the “Press PLC” node and the sensors user in the “Factory broker” node.
- Edit “Scale and name” to match your register map.
- Deploy. mosquitto_sub on the Pi shows factory/press-2/modbus every 5 s.
Node-RED flow: Modbus TCP → MQTT
[
{
"id": "iqm_tab",
"type": "tab",
"label": "PLC (Modbus TCP) → MQTT",
"disabled": false,
"info": "Reads 4 holding registers every 5 s and publishes them as JSON on factory/press-2/modbus. Needs node-red-contrib-modbus (Manage palette)."
},
{
"id": "iqm_client",
"type": "modbus-client",
"name": "Press PLC",
"clienttype": "tcp",
"bufferCommands": true,
"stateLogEnabled": false,
"queueLogEnabled": false,
"tcpHost": "192.168.1.50",
"tcpPort": "502",
"tcpType": "DEFAULT",
"serialPort": "",
"serialType": "RTU-BUFFERD",
"serialBaudrate": "9600",
"serialDatabits": "8",
"serialStopbits": "1",
"serialParity": "none",
"serialConnectionDelay": "100",
"serialAsciiResponseStartDelimiter": "0x3A",
"unit_id": "1",
"commandDelay": "1",
"clientTimeout": "1000",
"reconnectOnTimeout": true,
"reconnectTimeout": "2000",
"parallelUnitIdsAllowed": true
},
{
"id": "iqm_read",
"type": "modbus-read",
"z": "iqm_tab",
"name": "Holding 0–3",
"topic": "",
"showStatusActivities": false,
"logIOActivities": false,
"showErrors": true,
"unitid": "1",
"dataType": "HoldingRegister",
"adr": "0",
"quantity": "4",
"rate": "5",
"rateUnit": "s",
"delayOnStart": false,
"startDelayTime": "",
"server": "iqm_client",
"useIOFile": false,
"ioFile": "",
"useIOForPayload": false,
"emptyMsgOnFail": false,
"x": 130,
"y": 80,
"wires": [
[
"iqm_shape"
],
[]
]
},
{
"id": "iqm_shape",
"type": "function",
"z": "iqm_tab",
"name": "Scale and name",
"func": "// Registers 0..3 from the PLC → named signals with scaling. Edit to match your register map.\nconst r = msg.payload; // array of 16-bit values\nmsg.topic = 'factory/press-2/modbus';\nmsg.payload = {\n hydraulic_pressure_bar: r[0] / 10, // 0.1 bar per count\n oil_temp_c: r[1] / 10,\n motor_current_a: r[2] / 10,\n cycle_count: r[3]\n};\nreturn msg;",
"outputs": 1,
"timeout": 0,
"noerr": 0,
"initialize": "",
"finalize": "",
"libs": [],
"x": 330,
"y": 80,
"wires": [
[
"iqm_out"
]
]
},
{
"id": "iqm_broker",
"type": "mqtt-broker",
"name": "Factory broker",
"broker": "localhost",
"port": "1883",
"clientid": "plc-modbus",
"autoConnect": true,
"usetls": false,
"protocolVersion": "4",
"keepalive": "60",
"cleansession": true
},
{
"id": "iqm_out",
"type": "mqtt out",
"z": "iqm_tab",
"name": "factory/press-2/modbus",
"topic": "",
"qos": "1",
"retain": "false",
"broker": "iqm_broker",
"x": 560,
"y": 80,
"wires": []
}
]Set up the MQTT broker (once per plant)
The sensors publish their readings to a broker: a small program that receives MQTT messages and hands them to whoever subscribes. Mosquitto is free and runs on a Raspberry Pi, an old PC or a small industrial box on the plant network. You need one per plant, not one per machine. If you already have a broker (Node-RED, Home Assistant, an IoT gateway), use it and skip this step.
# Raspberry Pi OS, Debian or Ubuntu
sudo apt update
sudo apt install -y mosquitto mosquitto-clients
# One user for the sensors and one read-only user for testing
sudo mosquitto_passwd -c /etc/mosquitto/passwd sensors
sudo mosquitto_passwd /etc/mosquitto/passwd viewer# /etc/mosquitto/conf.d/factory.conf
listener 1883
allow_anonymous false
password_file /etc/mosquitto/passwd
acl_file /etc/mosquitto/acl# /etc/mosquitto/acl
user sensors
topic readwrite factory/#
user viewer
topic read factory/## Mosquitto 2 wants these files readable only by its own user
sudo chown mosquitto: /etc/mosquitto/passwd /etc/mosquitto/acl
sudo chmod 0700 /etc/mosquitto/passwd /etc/mosquitto/acl
sudo systemctl restart mosquitto
sudo systemctl enable mosquitto
# Watch everything that arrives (Ctrl+C to stop)
mosquitto_sub -h localhost -u viewer -P 'viewer-password' -t 'factory/#' -vCheck the readings with Claude before you connect anything
Before the data goes anywhere, make sure the sensor is telling the truth. Record two minutes of messages to a file and ask Claude (or ChatGPT) to check them. This catches the usual first-day problems (a clamp on the wrong cable, a probe reading the room instead of the pipe, a sensor that only reports when something changes) while you are still standing at the PLC.
# Record 2 minutes of messages to a file you can give Claude or ChatGPT
mosquitto_sub -h 192.168.1.20 -u viewer -P 'viewer-password' \
-t 'factory/#' -v -W 120 | while read -r line; do
echo "$(date -u +%Y-%m-%dT%H:%M:%SZ) $line"
done > sensor-sample.txt# Windows PowerShell, with Mosquitto installed from mosquitto.org
& "C:\Program Files\mosquitto\mosquitto_sub.exe" -h 192.168.1.20 -u viewer -P viewer-password `
-t "factory/#" -v -W 120 | ForEach-Object { "$(Get-Date -Format o) $_" } | Out-File sensor-sample.txtI've attached sensor-sample.txt: two minutes of MQTT messages from a sensor I just fitted to the PLC.
Each line is: time, topic, payload.
Please check it for me:
1. List each topic and every numeric field in it, with the min, max and typical value.
2. Tell me whether the values are physically plausible for the PLC. Compare each value with what the machine’s HMI shows at the same moment: they should agree within the scaling. A value that is always 0 or 65535 usually means the wrong register.
3. Point out gaps longer than 30 seconds, repeated identical values, or fields that are always 0.
4. Say which fields are worth sending to InduQT as signals and which I can ignore.
Answer in a short table, then a list of anything I should fix before I wire it up.Claude Code or Claude desktop with a terminal can run the mosquitto_sub command for you: ask it to "subscribe to factory/# on 192.168.1.20 as viewer for two minutes and check the readings". Either way the readings stay on your laptop: nothing is stored in InduQT until you wire it up in the next step.
Using a cloud broker (HiveMQ Cloud, EMQX Serverless or your own server with TLS) instead of one on the plant network? Add the free InduQT connector to Claude (https://claude.ai/directory/connectors/induqt) and Claude can listen to the broker for a few seconds itself:
Use InduQT to preview my MQTT broker before I connect it:
url mqtts://<your-cluster>.hivemq.cloud:8883, topic factory/#,
username viewer, password <viewer password>. Listen for 10 seconds.
Then tell me which topic level names the machine and which fields are numeric.Wire it to InduQT
Once the readings look right, send them to InduQT. The simplest way is a small bridge on the same Raspberry Pi: it listens to your broker and forwards every number to InduQT over HTTPS. It works on every InduQT plan, including the free one (up to 3 machines), and nothing on the plant network has to be opened to the internet.
- In Claude with the InduQT connector, paste the prompt below. Claude creates the site, the machine and a key that can only send readings to that site. (No Claude? Do the same in the InduQT app: Add machine with the same externalId, then Settings → API keys → a key with the ingest scope, limited to the site.)
- Copy the key Claude shows you. It is shown once.
- Start the bridge on the Raspberry Pi with that key.
- Ask Claude for the latest values, and set the normal bands.
Set up InduQT for this sensor:
1. Create a site called "Plant 1" (skip if it already exists).
2. Create a machine named "press-2" with externalId "press-2" and family "other".
3. Create an ingest key for the site called "Raspberry Pi bridge" and show it to me once.
After I start the bridge, I'll ask you to check the latest values. The signals will be hydraulic_pressure_bar, oil_temp_c, motor_current_a and cycle_count.python3 -m venv ~/induqt && source ~/induqt/bin/activate
pip install "paho-mqtt>=2.0" requests
export MQTT_HOST=localhost MQTT_USER=viewer MQTT_PASSWORD='viewer-password'
export MQTT_TOPICS='factory/#'
export INDUQT_API_KEY='iq_live_…' # the site key Claude or the app created for you
python3 induqt_bridge.pyinduqt_bridge.py (the whole bridge, about 120 lines)
#!/usr/bin/env python3
"""
induqt_bridge.py — forward MQTT sensor messages to InduQT.
Subscribes to your local broker, turns each message into numbers, and posts them
to the InduQT ingest API in batches. Works on every InduQT plan, including the free one,
and your broker never has to be reachable from the internet.
factory/<machine>/<anything> -> machine = <machine> (matched to the machine's externalId)
factory/pump-3/vibration {"vib_rms_x_g": 0.12} -> signal vib_rms_x_g
factory/comp-1/status/em:0 {"a_current": 12.4} -> signal em_0.a_current
(two or more levels after the machine: the last level names the group, so
two probes or two channels never overwrite each other)
{"temperature": {"tC": 41.2}} -> signal temperature.tC
factory/furnace-1/temp 21.7 -> signal temp (a bare number takes the last level)
pip install "paho-mqtt>=2.0" requests
"""
import json
import os
import re
import threading
import time
import paho.mqtt.client as mqtt
import requests
MQTT_HOST = os.environ.get("MQTT_HOST", "localhost")
MQTT_PORT = int(os.environ.get("MQTT_PORT", "1883"))
MQTT_USER = os.environ.get("MQTT_USER")
MQTT_PASSWORD = os.environ.get("MQTT_PASSWORD")
TOPICS = [t.strip() for t in os.environ.get("MQTT_TOPICS", "factory/#").split(",") if t.strip()]
MACHINE_LEVEL = int(os.environ.get("MACHINE_LEVEL", "1")) # factory/<machine>/... is level 1
SEND_EVERY = float(os.environ.get("SEND_EVERY", "10")) # seconds between posts
IGNORE = set(os.environ.get("IGNORE_FIELDS", "id,ts,time,timestamp,unixtime,Time").split(","))
INGEST_URL = os.environ.get("INDUQT_URL", "https://api.induqt.ai/v1/ingest")
API_KEY = os.environ["INDUQT_API_KEY"] # a site key from InduQT (Settings -> API keys)
BAD = re.compile(r"[^A-Za-z0-9_.\-]")
buffer, lock = [], threading.Lock()
def key(name):
return BAD.sub("_", name)[:64]
def numbers(prefix, value, out):
"""Collect every number in a JSON value; true/false become 1/0."""
if isinstance(value, bool):
out[key(prefix)] = 1 if value else 0
elif isinstance(value, (int, float)):
out[key(prefix)] = value
elif isinstance(value, str):
text = value.strip().lower()
if text in ("on", "true", "online"):
out[key(prefix)] = 1
elif text in ("off", "false", "offline"):
out[key(prefix)] = 0
else:
try:
out[key(prefix)] = float(text)
except ValueError:
pass
elif isinstance(value, dict):
for k, v in value.items():
if k not in IGNORE:
numbers(f"{prefix}.{k}" if prefix else k, v, out)
def on_connect(client, userdata, flags, reason_code, properties):
print(f"MQTT connected ({reason_code}); subscribing to {TOPICS}")
for t in TOPICS:
client.subscribe(t, qos=1)
def on_message(client, userdata, msg):
levels = msg.topic.split("/")
if len(levels) <= MACHINE_LEVEL:
return
machine = levels[MACHINE_LEVEL]
try:
payload = json.loads(msg.payload.decode("utf-8", "replace"))
except ValueError:
payload = msg.payload.decode("utf-8", "replace")
values = {}
group = levels[-1] if len(levels) - MACHINE_LEVEL > 2 else ""
if isinstance(payload, dict):
numbers(group, payload, values)
else:
numbers(levels[-1], payload, values)
if values:
with lock:
buffer.append({"machine": machine, "ts": int(time.time() * 1000), "values": values})
def sender():
while True:
time.sleep(SEND_EVERY)
with lock:
batch = buffer[:500]
if not batch:
continue
try:
r = requests.post(
INGEST_URL,
headers={"Authorization": f"Bearer {API_KEY}"},
json={"readings": batch, "autoCreate": True},
timeout=15,
)
if r.status_code < 300:
with lock:
del buffer[: len(batch)]
print(f"sent {len(batch)} readings: {r.json()}")
elif r.status_code in (400, 401, 403):
print(f"InduQT refused the batch ({r.status_code}): {r.text}")
with lock:
del buffer[: len(batch)] # fix the key or mapping; retrying will not help
else:
print(f"InduQT returned {r.status_code}; will retry")
except requests.RequestException as e:
print(f"network error, will retry: {e}")
with lock:
del buffer[:-5000] # keep at most ~5,000 readings while offline
client = mqtt.Client(mqtt.CallbackAPIVersion.VERSION2, client_id="induqt-bridge")
if MQTT_USER:
client.username_pw_set(MQTT_USER, MQTT_PASSWORD)
client.on_connect = on_connect
client.on_message = on_message
threading.Thread(target=sender, daemon=True).start()
client.connect(MQTT_HOST, MQTT_PORT, keepalive=60)
client.loop_forever()
Keep it running after a reboot (systemd)
# /etc/systemd/system/induqt-bridge.service — keeps the bridge running after a reboot
[Unit]
Description=MQTT to InduQT bridge
After=network-online.target mosquitto.service
[Service]
User=pi
EnvironmentFile=/home/pi/induqt-bridge.env
ExecStart=/home/pi/induqt/bin/python3 /home/pi/induqt_bridge.py
Restart=always
RestartSec=10
[Install]
WantedBy=multi-user.target
# then:
# sudo systemctl daemon-reload && sudo systemctl enable --now induqt-bridge
# journalctl -u induqt-bridge -fThe bridge treats the topic level after factory/ as the machine (it matches the machine's externalId and creates it if needed), turns every number in the message into a signal (nested fields become names like temperature.tC; when the topic has a group after the machine, such as Shelly's status/em:0, the group goes in front, as em_0.a_current, so two channels never overwrite each other; true/false and on/off become 1/0) and sends a batch every 10 seconds. It was run end to end on 2026-10-31 against Mosquitto 2 with Shelly Gen2, Theengs and plain-number messages. Prefer Node-RED? The same bridge as a Node-RED flow is on the gateway guide.
Show me the latest values InduQT has for press-2.
Then set these normal bands so InduQT knows what "normal" looks like: hydraulic_pressure_bar between 0 and the working pressure, oil_temp_c 30 to 60.On the Plant Monitor plan InduQT can also subscribe to a broker directly. Point your sensors (or a Mosquitto bridge) at a cloud broker with TLS, then ask Claude to "create an MQTT connector for this broker, machine from topic level 1", or add it in the app under the site → Connect data → MQTT broker.
What InduQT does with it
- Learns how the machine’s own signals move together and flags when one stops following the others.
- Names the signal that moved first when something goes wrong.
- Reads the machine’s manual (upload it) to explain alarm codes in context.
Frequently asked questions
Does this work with Siemens S7 or Allen-Bradley PLCs?
Yes, with other Node-RED nodes: node-red-contrib-s7 for S7 and node-red-contrib-cip-ethernet-ip for Logix. The flow shape is the same: read, scale and name, publish to MQTT. If the PLC has an OPC UA server, InduQT can read it directly.
Will this slow the PLC down?
Reading a few registers every few seconds is a tiny load for any modern PLC. Avoid polling hundreds of registers many times a second.