Siemens LME11 / LME21 / LME22 fault 5: Air pressure switch time supervision

Siemens LME11 / LME21 / LME22lockoutData sheet CC1N7101en, 20.05.2016

Five red blinks mean the air pressure switch was already in its working position when the burner control expected it at rest. A startup precondition is that the air pressure switch is in its no-load position; if it is welded in the working position, startup is prevented and a non-alterable lockout follows after 65 seconds.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Siemens LME11 / LME21 / LME22. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Where it sits in the burner

Supervised function: Combustion air proving.

ComponentSignals to look atHow it fails
Combustion air proving switchCombustion air proving switch, Combustion air pressurePressure or position switch out of adjustment; Welded, jumpered or miswired contact; Restricted combustion air path
Combustion air fan (FD / ID)Combustion fan running, Combustion fan speed, Combustion air pressure, Fan motor current, Fan vibrationRestricted combustion air path; Fan motor or drive fault; Bearing wear or misalignment
Burner management controllerBurner sequence state, Controller supply voltageController internal fault; Supply voltage, frequency or grounding problem; Configuration or commissioning data changed; Electrical noise on signal wiring

Likely causes and checks

1Air pressure switch contacts welded in working position

Points to it
Lockout on every start after about a minute; the switch reads made with the fan stopped.
Check
With power isolated and the fan stopped, check the switch contacts for continuity and replace a welded switch.

2Short circuit on the air pressure switch wiring

Points to it
Damaged cable, or work on the switch or plug-in base.
Check
The data sheet warns to check the air pressure switch connecting lines for short circuits (terminals 3, 6 and 11); a qualified electrician should check them with power isolated.

3Air still moving with the fan off

Points to it
Intermittent, linked to strong chimney draught, wind or another fan sharing the flue.
Check
Measure the pressure at the switch sensing point with the fan off and compare with the switch setting.

4Fan running when it should be off

Points to it
Fan audible during the waiting time.
Check
Check the fan motor supply and any external contactor that could keep the fan running.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.