Siemens LME11 / LME21 / LME22 fault 3: Air pressure switch faulty

Siemens LME11 / LME21 / LME22lockoutData sheet CC1N7101en, 20.05.2016

Three red blinks mean the burner control did not get the air pressure signal it expects. The data sheet lists loss of the air pressure signal after the specified time (t10), the air pressure switch welded in its normal (no-load) position, and a fault during valve proving when an LDU11 valve proving unit is used.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Siemens LME11 / LME21 / LME22. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Where it sits in the burner

Supervised functions: Combustion air proving, Purge, Valve proving and proof of closure.

ComponentSignals to look atHow it fails
Combustion air proving switchCombustion air proving switch, Combustion air pressurePressure or position switch out of adjustment; Welded, jumpered or miswired contact; Restricted combustion air path
Combustion air fan (FD / ID)Combustion fan running, Combustion fan speed, Combustion air pressure, Fan motor current, Fan vibrationRestricted combustion air path; Fan motor or drive fault; Bearing wear or misalignment
Main safety shutoff valvesMain fuel valve output, Valve proof of closureValve seat leakage or slow closing; Welded, jumpered or miswired contact; Fuel valve not opening fully
Burner management controllerBurner sequence state, Controller supply voltageController internal fault; Supply voltage, frequency or grounding problem; Configuration or commissioning data changed; Electrical noise on signal wiring

Likely causes and checks

1Fan not building air pressure

Points to it
Fan does not start, runs slowly or is noisy; motor or capacitor recently replaced.
Check
Watch the fan at start; check the fan motor, its capacitor and the motor output of the burner control.

2Air path or sensing line blocked

Points to it
Fan runs but the switch does not make; dirty fan wheel, blocked air inlet or flue, kinked or wet sensing tube.
Check
Measure the air pressure at the switch sensing point with the fan running and compare with the switch setting; clean the fan, inlet and sensing tube.

3Air pressure switch set too high or failing

Points to it
Intermittent 3 blinks, worse at some air settings or on windy days.
Check
Compare the switch setpoint with the burner maker’s setting and the measured pressure; replace a switch that does not switch cleanly.

4Air pressure switch welded in normal (no-load) position

Points to it
The switch never changes over, even with good air pressure.
Check
With power isolated, check the switch changeover contacts for continuity in both states.

5Fault during valve proving (LDU11 only)

Points to it
An LDU11 valve proving unit is fitted and the lockout comes before the fan sequence completes.
Check
Check the LDU11 indication and have the gas valves tightness-tested according to the LDU11 documentation.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.