Siemens LME11 / LME21 / LME22 troubleshooting

SiemensData sheet CC1N7101en, 20.05.2016

The Siemens LME11, LME21 and LME22 are burner controls for 1- or 2-stage gas burners of small to medium capacity, with flame supervision by ionization probe or a QRA UV detector. LME11 is for 1-stage burners, LME21 for 2-stage burners and LME22 for 2-stage burners with actuator control. A multicolour signal lamp in the lockout reset button shows the operating state and, after a lockout, the cause as a red blink code.

Diagnose this with AI

Upload a photo of the alarm screen, the fault history or a data export. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

How it reports faults

Operating sequence

  1. A: Start commandThe control thermostat or pressurestat calls for heat. All line contacts must be closed, the air pressure switch in its no-load position and the flame detector dark.
  2. tw: Waiting timeAbout 2.5 s. The lamp is off.
  3. t10: Air pressure signalThe fan runs and the air pressure switch must signal air within the specified time (5 s on LME11/LME21 types, 3 s on LME22 types). LME22 also drives the actuator open (t11) and closed (t12) around prepurge.
  4. t1: Prepurge timeMinimum 7 to 50 s depending on type (for example 20 s on LME21.230C2, 30 s on LME21.330C2). The lamp is yellow.
  5. t3: Preignition timeIgnition on before fuel: about 2 s (LME11/LME21) or 3 s (LME22). The lamp flashes yellow.
  6. TSA: Safety timeFuel valve 1 opens and flame must be established (B–B´): maximum 3 s, or 5 s on some LME21 types. No flame by the end gives 2 blinks.
  7. t3n / t4: Postignition and second stageIgnition stays on for the postignition time; after the interval t4 (about 8 or 10 s) fuel valve 2 is released on LME21 and LME22.
  8. C–D: Burner operationOperating position reached; the burner generates heat with the flame supervised (green lamp). D is the controlled shutdown by the thermostat or pressurestat. After at most 24 hours of continuous operation the LME makes a controlled shutdown and restart.

Fault codes

CodeName
2No establishment of flame at the end of safety time (TSA)
3Air pressure switch faulty
4Extraneous light when burner is started up
5Air pressure switch time supervision
7Too many losses of flame during operation (limitation of repetitions)
10Wiring error or internal error, output contacts, other faults
6Free (not used)
8–9Free (not used)
14CPI contact not closed (types with a closed position indicator input)

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.