Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000) fault T06:C01: Watchdog fault: task watchdog expired
A user task did not complete within its watchdog time. Rockwell lists three causes: a program error caused an infinite loop, the program is too complex to run as quickly as specified, or a higher-priority task is keeping this task from finishing. Corrective actions: increase the task watchdog, shorten execution time, raise the task priority, simplify higher-priority tasks, or move code to another controller.
Diagnose this with AI
Try Free PLC Fault Diagnostic Upload a keypad photo, the fault history or a parameter export from your Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000). InduQT compares the evidence and suggests the next useful checks.
When it happens
- In Run, when a task scan exceeds its watchdog
- After a program change that added loops or logic
Likely causes and checks
1Infinite or very long loop (JMP/LBL, FOR, WHILE)
- Points to it
- Fault after an edit that added a loop; scan time jumps rather than creeps.
- Check
- Review loops in the faulted task for an exit condition that can fail to be met.
2Task has more logic than its watchdog allows
- Points to it
- Task scan times (Task Properties > Monitor) trend close to the watchdog before the fault.
- Check
- Compare maximum scan time with the watchdog; profile which programs take the time.
3Higher-priority tasks starve this task
- Points to it
- Periodic or event tasks with higher priority run often or long; the faulted task itself is small.
- Check
- Review task priorities, periods and their scan times; check for task overlaps in the minor faults.
Telling it apart
- Raising the watchdog only hides an infinite loop; find out whether the task normally finishes well within it before changing the setting.
- Task overlap shows as a minor fault (FaultLog MinorFaultBits bit 6) and is a warning sign that tasks are competing for time.
- Type 6 faults are handled by the Controller Fault Handler, not the program fault routine.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| Task Properties > Configuration | Task watchdog | Time the task may run before T06:C01; increase only after confirming the cause. |
| Task Properties > Configuration | Task priority and period | Higher-priority tasks interrupt this one; Rockwell lists priority changes as a corrective action. |
Evidence to collect
- Major Faults tab screenshot (names the task)
- Task Properties: watchdog, priority, period and max scan time
- Minor Faults tab (task overlaps)
- Program export of the task’s programs
- Recent online edits
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.