WEG CFW500 fault F0070: Overcurrent/short-circuit

WEG CFW500faultSoftware version 2.0X

Overcurrent or short circuit on the output, the DC link or the braking resistor. The protection acts in hardware and cuts the output PWM pulses instantly; it corresponds to an overcurrent between output phases. The trip level depends on the power module and is well above the inverter’s rated current (P0295).

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your WEG CFW500. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Short circuit between two motor phases

Points to it
Trips instantly at start, even with no load.
Check
With the motor disconnected from the inverter, check the motor and motor cable phase to phase.

2Short circuit in the braking resistor cables

Points to it
A braking resistor is fitted; trips when braking or at power-up of the output.
Check
Inspect the braking resistor and its connecting cables.

3IGBT module short-circuited or damaged

Points to it
Trips immediately even with the motor disconnected.
Check
The power module is inside the inverter; refer to WEG service.

4Start with too short an acceleration ramp

Points to it
Trips partway through the ramp; fewer trips with a longer ramp or lighter load.
Check
Check P0100 and the current limitation settings P0135 and P0150.

5Start with the motor spinning and Flying Start off

Points to it
Trips when starting a fan or load that is still turning.
Check
Check P0320 (Flying Start) for loads that may still be turning at start.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
P0100Acceleration timeToo short a ramp is a listed cause.
P0135Maximum output current (V/f, VVW)Current limitation level; holding or reducing the ramp at this level prevents F0070.
P0150Type of DC link and current regulator (V/f, VVW)Selects Ramp Hold or Decelerate Ramp for current limitation.
P0320Flying Start / Ride-ThroughFlying Start lets the inverter start a motor that is already spinning.
P0340Auto-reset timeCan reset faults automatically; only enable once the cause is understood.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.