4-20 mA pressure transmitter reads below 4 mA or zero on PLC, what to check?

Question

I have a 4-20 mA pressure transmitter that is reading below 4 mA or even zero on my PLC analog input. The process pressure is definitely not zero. What should I check first to troubleshoot this?

Top answer · Written by InduQT from general maintenance practice; check against your own manual · Nov 4, 2026

When a 4-20 mA pressure transmitter reads below 4 mA or zero, it indicates a problem with the signal loop, power, or the transmitter itself. This usually means the PLC isn't receiving a valid signal. Start by verifying the loop power and checking the wiring connections.

Likely causes and checks

1Loss of Loop Power

Points to it
The transmitter requires external power to operate and generate the 4-20 mA signal. If the power supply is off, failed, or disconnected, the transmitter cannot send a signal, resulting in 0 mA.
Check
With the loop powered, using a meter rated for it, measure the DC voltage at the transmitter's power terminals. It should typically be 24 VDC. Also, check the fuse on the power supply or input card.

2Open Circuit or Wiring Fault

Points to it
A break in the wiring, a loose connection, or a damaged cable will prevent the current from flowing through the loop, causing the PLC to read 0 mA or a very low value.
Check
Isolate and lock out the circuit. Visually inspect all wiring from the power supply, through the transmitter, to the PLC input for damage or loose terminals. Use a multimeter to check for continuity across the loop, especially at junction boxes and terminal blocks.

3Failed Transmitter

Points to it
If the transmitter itself has failed internally, it may stop generating a current signal, even with proper power. This can happen due to internal component failure, damage, or age.
Check
Isolate and lock out the circuit. Disconnect the transmitter from the loop. Use a calibrated current source to inject a known 4-20 mA signal into the PLC input to verify the PLC and wiring are working. If they are, reconnect the transmitter and measure the current directly in series with the transmitter using a multimeter. If it reads 0 mA or an incorrect value despite proper power and pressure, the transmitter is likely faulty.

Next check: After checking power and wiring, if the problem persists, use a multimeter to measure the current directly in series with the transmitter to confirm if the transmitter is outputting a signal. If it's not, consider replacing the transmitter.

What it typically looks like in the data

Signal Loss0 min1 min2 min3 min4 min5 min50.349.7Process Pressure (psi)12.10Low Signal AlarmTransmitter Output (mA)
A loss of loop power or an open circuit causes the 4-20 mA signal to drop to zero, while the actual pressure remains stable. Illustrative, synthetic data showing the typical pattern, not a recording from a real machine; values vary by machine and settings.
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.