Thermocouple reading jumping or showing open-sensor value?

Question

I have a thermocouple connected to a PLC, and the temperature reading is either jumping erratically or showing a constant high value, like an open-sensor reading. What should I check first?

Top answer · Written by InduQT from general maintenance practice; check against your own manual · Nov 4, 2026

Erratic or open-sensor readings from a thermocouple often point to issues with the sensor's connection to the controller. These sensors generate very small voltages, making them highly susceptible to interference and connection problems. Start by inspecting the physical connections and wiring.

Likely causes and checks

1Loose or corroded connections

Points to it
Intermittent readings, sudden jumps, or complete loss of signal can be caused by poor contact at the terminal block or sensor head. Corrosion increases resistance and can generate spurious voltages.
Check
Isolate and lock out power to the PLC and sensor circuit. Visually inspect all terminal connections from the thermocouple to the PLC input module. Gently tug on wires to check for looseness. Look for signs of corrosion or damage on the wire ends and terminals. Clean and re-terminate if necessary.

2Incorrect thermocouple extension wire

Points to it
Using standard copper wire or the wrong type of thermocouple extension wire (e.g., Type K wire for a Type J thermocouple) will introduce a cold junction error, leading to incorrect and potentially unstable readings.
Check
Verify that the extension wire used matches the thermocouple type (e.g., Type J thermocouple uses Type J extension wire). The wire insulation should be color-coded according to standards (e.g., ANSI, IEC). Ensure the polarity is correct (+ to + and - to -) at all connection points.

3Electrical noise or poor grounding

Points to it
Thermocouples produce millivolt signals, making them very sensitive to electromagnetic interference (EMI) from motors, VFDs, or power cables. Poor grounding can create ground loops, causing fluctuating readings.
Check
Check if the thermocouple wiring is routed separately from power cables and other sources of electrical noise. Ensure the PLC and sensor shielding (if present) are properly grounded to a common, clean ground point. Look for missing or damaged shield connections.

4Damaged thermocouple or input module

Points to it
If all wiring and connection checks pass, the sensor itself or the PLC input module might be faulty. An internal break in the thermocouple or a damaged input channel can cause open-circuit readings or erratic behavior.
Check
Disconnect the thermocouple from the PLC. Use a multimeter to check the thermocouple's resistance (should be low, a few ohms) and for an open circuit. If possible, temporarily connect a known good thermocouple to the PLC input to see if the problem persists. If the issue resolves, the original thermocouple is likely bad. If not, the PLC input module may be at fault.

Next check: After checking connections and wiring, if the problem persists, consider temporarily replacing the thermocouple with a known good one to rule out sensor failure.

What it typically looks like in the data

Erratic/Open reading0 min1 min2 min3 min4 min5 min50149.6Open circuit detectionTemperature (°C)
A thermocouple reading showing an open circuit or erratic behavior due to connection issues or noise. Illustrative, synthetic data showing the typical pattern, not a recording from a real machine; values vary by machine and settings.
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.